Haes MZAOV-1003 AOV Control Panel - Two Zone (Extendable To 8)

SKU
MZAOV-1003
AED4,312.94 AED5,175.53
Enquire about this product
  • Manufacturer : Haes
  • Part Code : MZAOV-1003
  • Two Zone AOV Control Panel
  • Extendable to Eight Zones

Haes MZAOV-1003 AOV Control Panel

The Haes MZAOV-1003 is a two detection zone, (extendable to 8), smoke vent control panel with integral 10 amp power supply, designed to control 24vdc actuators or magnets.

The panel has battery backup capability and assures that actuators can be powered in the event of a mains failure.

Vent controls and indications are provided on the front of the control panel with a large graphical LCD display and integral control inputs to accept signals from remote contacts, smoke detectors and manual controls.

Optional support for Rain Sensor and PIR inputs for environmental control and trap injury protection, plus 0/10v inputs and outputs to allow control interfacing with BMS systems and positional control Act output.

The MZAOV control panel range has been developed to provide a comprehensive solution to smoke vent control scenarios.

Haes MZAOV-1003 AOV Control Panel Features

  • 10 amp integral PSU
  • Large graphical display
  • Easy to program
  • Up to 8 detection zones, Conventional and Twin-wire
  • Upto 8 Input from other detection systems, to activate
  • Upto 8 Monitored Actuator outputs for controlling smoke vents
  • Switch input to control wide combination of vents
  • Fireman switch input to override all other inputs
  • All inputs and actuator outputs monitored for Short and Open Circuit
  • User switch inputs configurable as local fireman switches
  • Thermostat input - Ventilation mode. Vents openable in 10% steps
  • Optional support for Rain sensor, PIR and BMS control
  • Monitoring of unused inputs and outputs can be disabled
  • Actuators configurable for independent operation or linked together as per required by 12101-9
  • Staggered start of actuators to avoid the combined start-up currents from simultaneous actuator activations

Haes MZAOV-1003 AOV Control Panel Specification

  • Enclosure : 1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat
  • Cable Entry : Via 20mm knockouts located in the top and rear of the cabinet
  • Dimensions Back box : 490mm W x 460mm H x 110mm D
  • Lid : 470mm W x 500mm H x 25mm D
  • Mains Supply : 10A internal switch mode power supply, Nom 27v DC
  • Battery Capacity : 2 x 18Ah 12v VRLA
  • Detection Zones : 1 to 8 monitored detection zones. EOL = 6K8
  • Twin Wire : Selectable in panel (enables AV devices to be connected to det cct)
  • On Board Relays : 1 x Alarm, 1 x Fault, volt free changeover, Max 3A
  • Fireman’s Switch Input : Fireman’s control switch input for Open/Close/Auto
  • Vent Control Input : 1 to 8 vent control switch inputs, Open/Close (rocker switch)
  • Actuator Output : 1 to 8 reversal actuator control output (9A total max) can be configured as a maintained output for a magnetic door
  • Aux Output : 1 to 8 voltage free normally open relay contacts, closing when the associated zone is activated, Max 3A
  • BMS Connection : 0/10v positional control input 10% steps, 0/10v positional data output. (Available on separate PCB)
  • False Alarm Management : Type A, B and C dependency mode, approved by LPCB